An air conditioner does not sense room temperature. It senses the temperature of a piece of copper that is touching it, which is why the sensor is specified as a sleeve rather than as a probe with a head on it. The whole design question is how much of a temperature difference the copper is allowed to introduce between the air in the duct and the thermistor bead sitting inside it.
The competing requirements are what make this part awkward. The sleeve has to conduct heat well, so the air temperature reaches the sensor. It has to seal refrigerant, so it has to be a closed pressure boundary. It has to be formable from thin copper tube, so it can be rolled into the belly that fits the capillary. And it has to carry only two or three thin wires out of it without creating a leak path.
What the B25/85 number actually commits you to
The 5K, 10K, 15K, 20K and 50K designations are the thermistor’s resistance at 25 degrees Celsius. The higher the number, the flatter the curve in the range where the sensor spends most of its life.
- 5K and 10K are steep in the duct range. The sensor moves a large resistance for a small temperature change, so it resolves small differences well. Air conditioners typically use 10K for a duct sensor and 5K where the control expects a steeper signal.
- 15K and 20K sit in the middle. They give a smoother, more linear-looking characteristic across a wide band, which suits sensors that also have to work in a cold evaporator or in a mixed-air position.
- 50K is deliberately flat. It is the choice where the sensing range spans a wide temperature interval and the controller only needs direction and rough magnitude, not resolution.
The practical consequence is the resistance the control board expects. A 10K sensor with a 10K pull-up and a divider network will not simply substitute a 15K part; the control calibration changes. On a replacement or a variant build, the B-value has to be treated as part of the electrical specification, not as a generic sensor.
Wall thickness decides the measurement error
Here is the trade that people get wrong. Copper conducts heat about twenty times better than air, so a thick copper sleeve will track the copper temperature very closely. But a thick sleeve also carries thermal mass, and thermal mass means the sensor lags. In a cycling air conditioner, a sensor that lags by a couple of degrees is a sensor that short-cycles.
The sleeve is normally made from copper of the thinnest wall the forming equipment can hold without ovality. The reference versions of this part are built from 0.8mm to around 1.2mm wall, and the drawing should state the wall band explicitly rather than leaving it to the tube mill. Copper tube arrives with its own wall tolerance, and a sleeve made from a heavy-wall coil will measure differently from one made from a light-wall coil even though both are nominally the same part.
Once the sleeve wall is fixed, the remaining error comes from the fit between the thermistor bead and the inside of the sleeve. A bead rattling inside a loose sleeve reads air temperature, not copper temperature, and the reading will vary with airflow direction and vibration. The fit is normally closed with a thermal filler — a silicone or epoxy-based compound that conducts and does not flow at operating temperature. That filler choice is a reliability decision: a filler that softens and migrates over ten years of heat cycling will eventually leave an air gap in the middle of the sleeve.
Rolling the belly is a forming problem with a sealing consequence
The sleeve is not a straight tube. It has a belly or a shoulder that seats against the capillary, and forming that belly is a roll-forming operation performed after the thermistor and wires are already inside.
That ordering is deliberate. If the sleeve were formed first and the bead inserted afterwards, the bead would have to pass through the bore, and the wires would have to be threaded through the smallest section. By loading the sensor first, the bead can be positioned exactly and the leads bent to a fixed geometry before the metal closes around them. It also means the bead is never abraded by being dragged through the bore.
The consequence is that the seal is made last, by deformation of the tube wall. Where the sleeve flattens onto the capillary, two things must be true simultaneously:
- The flattening must be tight enough to seal the system against refrigerant pressure at temperature, including the pressure that occurs when the system is not yet running and the refrigerant is at ambient temperature.
- The flattening must not be so aggressive that it collapses the capillary. A copper capillary is already a thin-wall, work-hardened part; a squeeze that looks cosmetically correct can reduce its bore enough to change the flow rating of the whole circuit.
Hermetic testing at full design pressure and at cycle temperature is the only real confirmation. A helium leak check is the standard, and it is worth specifying on the drawing because it distinguishes a leak path through the flattening from a leak path through the wire exit.
Where the wires leave the sleeve, and why two or three
The wire exit is the weakest point in the whole assembly and it is where most returns originate.
The lead count is a product decision that shows up in the mechanical design. Two wires is the minimum: thermistor lead and thermistor lead, with the thermistor itself providing the resistance. That is the cleanest arrangement thermodynamically, because no additional metal sits in the thermal path.
Three wires appear when the manufacturer wants a connection that distinguishes the sensor from a shorted or open thermistor at the board level, or where the sensor shares a common conductor with another element. Every additional conductor is another hole in the pressure boundary, and each hole is a potential leak path that has to be sealed after insertion.
The sealing method is the part to specify. Options include:
- Epoxy or silicone potting over the wire exit, which is simple and adequate at moderate temperatures.
- A glass-to-metal hermetic seal, which is more expensive and gives a much wider temperature rating and a far lower leak rate.
- A strain-relief sleeve inside the copper, which does nothing for sealing but prevents the mechanical loads from being transferred to the wire entry directly.
Note that the filler used between bead and sleeve and the sealant used at the wire exit are different materials solving different problems. Specifying one material for both roles is a common error: a thermal filler chosen for its high conductivity after cure is not usually the best sealant for a pressure boundary, and vice versa.
Finish, corrosion and what happens at the evaporator
Copper sleeves that sit in an evaporator or in a humid drain pan get a surface treatment, usually tin plating or a nickel layer, and the reason is not appearance. Bare copper in a wet, oxygenated environment develops a dark oxide scale, and in the presence of flux residue and moisture that scale is a poor thermal conductor. A plated sleeve transfers heat more consistently across its service life than a bare one, and the plating also resists the mild corrosion that eventually thins the wall at the seal face.
For a sensor used in a hermetic refrigerant circuit, passivation or tin plating also matters because it reduces the chance of galvanic attack where the copper sleeve touches an aluminium or brass component.
Questions worth asking about this sensor
These are the details that decide whether the sensor measures correctly on the first build:
- Which B-value is specified, and is it tied to the controller calibration rather than described loosely as a 10K thermistor?
- What is the sleeve wall thickness band, and is it specified separately from the copper tube grade and temper?
- How is the thermistor located in the bore, and what thermal filler closes the gap between bead and copper?
- What is the wire exit construction — potting, glass-to-metal, or both — and how many conductors does the board expect?
- Is there a strain relief between the wire exit and the belly, so that flexing at the capillary does not work the seal?
- For an evaporator position, is the surface treatment specified, and has the assembly been leak-tested at cycle temperature rather than only at room temperature?
The last one is worth insisting on. A sleeve that passes a room-temperature pressure test can still fail its first cold cycle, because the flattening seal is loaded differently when the copper is cold and the refrigerant is not. Testing at cycle temperature is the only test that reproduces the actual failure mode.
Deep Drawn Tubes & Sleeves is the parent range for parts like this one; the overview page gathers the tooling logic, finishing options and tolerance notes that apply across the family.
Specifications
| Item | Air Conditioner Copper Sensor Sleeves |
|---|---|
| Brand | AUNOV |
| Designing | The drawing is reviewed first; the agreed version then governs every batch. |
| Tooling | Because tooling is in house, changes to the part can be trialled without waiting on a third party. |
| Samples | Prototype and pre-production samples are provided against the drawing, so any deviation is corrected at sample stage, and mass production is gated on that approval. |
| Materials | T2 / T3 copper and H62 brass, 0.8-4.0 mm; soft tempers for deep forming, hard tempers where stiffness matters. |
| Surface finish | Finish selected from the drawing: plating, coating, anodising or passivation; alternatives quoted with the quotation, samples approved in writing. |
| Processing | Tube drawing, straightening and turning in one flow; every stage is logged against your part number. |
| Equipment | Drawn-tube benches, in-line annealing and CNC turning, backed by CNC turning centres and a climate-controlled inspection room. |
| Tolerance | +/-0.02 mm on turned diameters, wall held to the agreed band; dimensional reports accompany the first article. |
| Delivery terms | Incoterms FOB as standard with DDP on request; sea and air options priced with the order. |
Related Products
Frequently Asked Questions
Why is an AC temperature sensor specified as a sleeve rather than a probe?
An air conditioner does not sense room temperature, it senses the temperature of a piece of copper that is touching it, which is why the sensor is a sleeve rather than a probe with a head on it. The whole design question is how much temperature difference the copper is allowed to introduce between the duct air and the thermistor bead inside it. Copper conducts heat about twenty times better than air, so a thick sleeve tracks the copper temperature very closely.
What does the B25/85 number actually commit you to?
It commits the thermistor’s resistance-temperature curve, and it is the number that decides how the sleeve’s error is interpreted. The sleeve is normally made from the thinnest copper wall the forming equipment can hold without ovality, because a heavy-wall coil measures differently from a light-wall coil even at the same nominal size. A bead rattling inside a loose sleeve reads air temperature, not copper temperature, and the reading varies with airflow and vibration.
Why is rolling the belly a forming problem with a sealing consequence?
The sleeve has to be formable from thin copper tube so it can be rolled into the belly that fits the capillary, and that roll sets the wall where the seal later sits. If the sleeve were formed first and the bead inserted afterwards, the bead would have to pass through the bore and the wires through the smallest section. Forming around the bead instead means it is never abraded by being dragged through the bore.
Why do copper sleeves in an evaporator get a surface treatment?
Bare copper in a wet, oxygenated environment develops a dark oxide scale, and with flux residue and moisture that scale is a poor thermal conductor. A plated sleeve, usually tin or nickel, transfers heat more consistently across its service life and resists the mild corrosion that thins the wall at the seal face. For a hermetic refrigerant circuit, passivation or tin plating also reduces galvanic attack where the copper touches an aluminium or brass component.